Detail ABB 1SBL397001R1211 AF80-30-11-12 48-130V50/60HZ-DC Contactor
Perlengkapan Listrik Lainnya
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
1
Standards:
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage:
Auxiliary Circuit 690 V
Main Circuit 1000 V
Rated Frequency (f):
Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 125 A
(690 V) 60 °C 100 A
(690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie):
(415 V) 60 °C 80 A
(440 V) 60 °C 80 A
(500 V) 60 °C 65 A
(690 V) 60 °C 49 A
(1000 V) 60 °C 25 A
(380 / 400 V) 60 °C 80 A
(220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie):
(415 V) 60 °C 80 A
(440 V) 60 °C 80 A
(500 V) 60 °C 65 A
(690 V) 60 °C 49 A
(380 / 400 V) 60 °C 80 A
(220 / 230 / 240 V) 60 °C 80 A
Rated Operational Power AC-3 (Pe):
(400 V) 37 kW
(415 V) 45 kW
(440 V) 45 kW
(500 V) 45 kW
(690 V) 45 kW
(1000 V) 35 kW
(380 / 400 V) 37 kW
(220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe):
(415 V) 45 kW
(440 V) 45 kW
(500 V) 45 kW
(690 V) 45 kW
(380 / 400 V) 37 kW
(220 / 230 / 240 V) 22 kW
Rated Operational Current AC-15 (Ie):
(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Maximum Electrical Switching Frequency:
(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Rated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 °C 125 A
(110 V) 2 Poles in Series, 60 °C 100 A
(110 V) 2 Poles in Series, 70 °C 85 A
(110 V) 3 Poles in Series, 40 °C 125 A
(110 V) 3 Poles in Series, 60 °C 100 A
(110 V) 3 Poles in Series, 70 °C 85 A
(220 V) 3 Poles in Series, 40 °C 125 A
(220 V) 3 Poles in Series, 60 °C 100 A
(220 V) 3 Poles in Series, 70 °C 85 A
(72 V) 1-Pole, 40 °C 125 A
(72 V) 1-Pole, 60 °C 100 A
(72 V) 1-Pole, 70 °C 85 A
(72 V) 2 Poles in Series, 40 °C 125 A
(72 V) 2 Poles in Series, 60 °C 100 A
(72 V) 2 Poles in Series, 70 °C 85 A
(72 V) 3 Poles in Series, 40 °C 125 A
(72 V) 3 Poles in Series, 60 °C 100 A
(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 °C 125 A
(110 V) 2 Poles in Series, 60 °C 100 A
(110 V) 2 Poles in Series, 70 °C 85 A
(110 V) 3 Poles in Series, 40 °C 125 A
(110 V) 3 Poles in Series, 60 °C 100 A
(110 V) 3 Poles in Series, 70 °C 85 A
(220 V) 3 Poles in Series, 40 °C 125 A
(220 V) 3 Poles in Series, 60 °C 100 A
(220 V) 3 Poles in Series, 70 °C 85 A
(72 V) 1-Pole, 40 °C 125 A
(72 V) 1-Pole, 60 °C 100 A
(72 V) 1-Pole, 70 °C 85 A
(72 V) 2 Poles in Series, 40 °C 125 A
(72 V) 2 Poles in Series, 60 °C 100 A
(72 V) 2 Poles in Series, 70 °C 85 A
(72 V) 3 Poles in Series, 40 °C 125 A
(72 V) 3 Poles in Series, 60 °C 100 A
(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 °C 125 A
(110 V) 2 Poles in Series, 60 °C 100 A
(110 V) 2 Poles in Series, 70 °C 85 A
(110 V) 3 Poles in Series, 40 °C 125 A
(110 V) 3 Poles in Series, 60 °C 100 A
(110 V) 3 Poles in Series, 70 °C 85 A
(220 V) 3 Poles in Series, 40 °C 125 A
(220 V) 3 Poles in Series, 60 °C 100 A
(220 V) 3 Poles in Series, 70 °C 85 A
(72 V) 1-Pole, 40 °C 125 A
(72 V) 1-Pole, 60 °C 100 A
(72 V) 1-Pole, 70 °C 85 A
(72 V) 2 Poles in Series, 40 °C 125 A
(72 V) 2 Poles in Series, 60 °C 100 A
(72 V) 2 Poles in Series, 70 °C 85 A
(72 V) 3 Poles in Series, 40 °C 125 A
(72 V) 3 Poles in Series, 60 °C 100 A
(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie):
(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 1000 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Rated Control Circuit Voltage (Uc):
50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Coil Consumption:
Average Holding Value 50 / 60 Hz 4 V·A
Average Holding Value 50 Hz 4 V·A
Average Holding Value 60 Hz 4 V·A
Average Holding Value DC 2 W
Average Holding Value, from Warm State 2 W
Operate Time:
Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied):
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 6 ... 50 mm²
Flexible with Insulated Ferrule 1/2x 6 ... 50 mm²
Rigid Stranded 1x 6 ... 70 mm²
Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length:
Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 17 mm
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type:
Screw Terminals
Tampilkan Lebih Banyak