Detail ABB CM-PVS.41S MULTIFUNTION RILEY MONITORING RMS 3PH 1SVR730794R330
Perlengkapan Listrik Lainnya
Function:
Phase failure detection
Phase sequence monitoring
Over- and undervoltage monitoring
Measuring Range:
(L-L) 300 ... 500 V AC
Time Range:
200 ms start-up delay
0 s or 0.1 ... 30 s tripping delay (ON or OFF)
Rated Control Supply Voltage (Us):
(L-L) 300 ... 500 V AC
Rated Frequency (f):
Supply Circuit 50/60 Hz
Output:
2 c/o (SPDT) contacts
Terminal Type:
Screw Terminals
Rated Operational Current AC-12 (Ie):
(230 V) 4 A
Rated Operational Current AC-15 (Ie):
(230 V) 3 A
Rated Operational Current DC-12 (Ie):
(24 V) 4 A
Rated Operational Current DC-13 (Ie):
(24 V) 2 A
Minimum Switching Capacity:
24 V
10 mA
Rated Impulse Withstand Voltage (Uimp):
Input Circuit 6 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui):
Input Circuit / Output Circuit 600 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of Protection:
Housing IP50
Terminals IP20
Overvoltage Category:
III
Pollution Degree:
3
Short-Circuit Protective Devices:
Output Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical Durability:
AC-12 100000 cycle
Mechanical Durability:
30000000 cycle
Connecting Capacity:
Flexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque:
0.6 ... 0.8 N·m
Wire Stripping Length:
8 mm
Recommended Screw Driver:
0.8 x 4
4.5
Pozidriv 1
Mounting Position:
1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Tampilkan Lebih Banyak