Detail ABB KONTAKTOR 3PH 150A 110VAC 1NO 1NC AX150-30-11 1SFL991074R8411
Perlengkapan Listrik Lainnya
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
1
Rated Operational Voltage:
Main Circuit 1000 V
Rated Frequency (f):
Main Circuit 50 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 190 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 190 A
(690 V) 55 °C 145 A
(690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie):
(415 V) 55 °C 150 A
(440 V) 55 °C 100 A
(500 V) 55 °C 100 A
(690 V) 55 °C 82 A
(380 / 400 V) 55 °C 150 A
(220 / 230 / 240 V) 55 °C 150
Rated Operational Power AC-3 (Pe):
(415 V) 75 kW
(440 V) 59 kW
(500 V) 59 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 45 kW
Rated Breaking Capacity AC-3:
8 x Ie AC-3
Rated Making Capacity AC-3:
10 x Ie AC-3
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
Maximum Electrical Switching Frequency:
300 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Mechanical Durability:
10 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc):
50 Hz 110 V
60 Hz 110 ... 120 V
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type:
Main Circuit: Bars
Tampilkan Lebih Banyak