Detail ABB KONTAKTOR KAPASITOR UA30-30-10RA 220-230V 50HZ / 230-240V 60HZ
Perlengkapan Listrik Lainnya
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
0
Standards:
IEC/EN 60947-1, IEC/EN 60947-4-1
Rated Operational Voltage:
Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f):
Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Power AC-6b (Pe):
(230 / 240 V) 40 °C, 50 / 60 Hz 16 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 16 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 30 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 19.5 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 27.5 kvar
(440 V) 40 °C, 50 / 60 Hz 32 kvar
(440 V) 55 °C, 50 / 60 Hz 30 kvar
(440 V) 70 °C, 50 / 60 Hz 20.5 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 34 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 34 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 25 kvar
(690 V) 40 °C, 50 / 60 Hz 45 kvar
(690 V) 55 °C, 50 / 60 Hz 45 kvar
(690 V) 70 °C, 50 / 60 Hz 32 kvar
Rated Operational Current AC-15 (Ie):
(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Short-Circuit Protective Devices:
Auxiliary Circuit - gG Type Fuses 10 A
gG Type Fuses 200 A
Rated Short-time Withstand Current Low Voltage (Icw):
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
Maximum Electrical Switching Frequency:
240 cycles per hour
Rated Operational Current DC-13 (Ie):
(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 2 / 144 W
(110 V) 1.1 A / 121 W
(125 V) 1.1 / 138 W
(220 V) 0.55 A / 121 W
(250 V) 0.55 / 138 W
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 1000 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Control Circuit Voltage (Uc):
50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Coil Consumption:
Average Holding Value 50 / 60 Hz 12 V·A
Average Holding Value 50 Hz 12 V·A
Average Holding Value 60 Hz 12 V·A
Average Pull-in Value 50 Hz 120 V·A
Average Pull-in Value 60 Hz 140 V·A
Operate Time:
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NO Contact Closing 8 ... 21 ms
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied):
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit:
Flexible with Cable End 2.5 ... 4 mm²
Rigid Cable 2.5 ... 6 mm²
Connecting Capacity Auxiliary Circuit:
Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Connecting Terminals (delivered in open position) Main Poles:
M 5 (+,-) pozidriv 2 screws with 2x (5.6x6.5 mm) connector
Terminal Type:
Screw Terminals