Detail ABB MANUAL MOTOR STATER 54A 45KW MO165-54 1SAM461000R1016
Perlengkapan Listrik Lainnya
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 30 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 50 kA
(250 V DC) 100 kA
(400 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 20 kA
(690 V AC) 8 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):
810 A
Setting Range:
None
Rated Operational Power AC-3 (Pe):
(400 V) Three Phase 22 kW
Rated Operational Power AC-3e (Pe):
(400 V) Three Phase 22 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie):
54 A
Rated Operational Current AC-3 (Ie):
54 A
Rated Operational Current AC-3e (Ie):
54 A
Rated Operational Current DC-5 (Ie):
54 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw):
0 ... 415 Hz
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Rated Insulation Voltage (Ui):
1000 V
Power Loss:
7 W
Number of Poles:
3
Conventional Free-air Thermal Current (Ith):
Main Circuit 54 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree:
3
Electrical Durability:
25000 cycle
Mechanical Durability:
50000 cycle
Terminal Type:
Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²
Flexible 1/2x 1 ... 35 mm²
Rigid 1/2x 1 ... 4 mm²
Solid 1/2x 1 ... 4 mm²
Stranded 1/2x 1 ... 50 mm²
Tightening Torque:
Main Circuit 4 N·m
Wire Stripping Length:
Main Circuit 16 mm
Recommended Screw Driver:
Pozidriv 2
Mounting Position:
1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type:
Rotary Handle
Contact Position Indication:
ON / OFF / TRIP
Standards:
CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-4-1
Tampilkan Lebih Banyak